65286 0xFF06 Motor overspeed Keypad display: Motor overspeed
Cause Error type/response Remedy
The motor speed has reached the error thresh-
old for overspeed set in 0x2D44:001 (P350.01).
Fault (Congurable)
•
The error can only be reset aer a blocking
me.
Check applicaon.
Blocking me: 1 s
Seng parameters: 0x2D44:002 (P350.02)
Related topics
4Motor speed monitoring ^ 237
65289 0xFF09 Motor phase missing Keypad display: Mot.Phase miss.
Cause Error type/response Remedy
A failure of several motor phases has been
detected.
No response (Congurable)
•
The error can only be reset aer a blocking
me.
•
Check wiring between inverter and motor.
•
In case of a false tripping, adapt the sengs
for the motor phase failure detecon.
Blocking me: 2 s
Seng parameters: 0x2D45:001 (P310.01)
Related topics
4Motor phase failure detecon ^ 236
65290 0xFF0A Motor phase failure phase U Keypad display: Phase U failure
Cause Error type/response Remedy
A failure of the motor phase U has been detec-
ted.
No response (Congurable)
•
The error can only be reset aer a blocking
me.
•
Check wiring between inverter and motor.
•
In case of a false tripping, adapt the sengs
for the motor phase failure detecon.
Blocking me: 2 s
Seng parameters: 0x2D45:001 (P310.01)
Related topics
4Motor phase failure detecon ^ 236
65291 0xFF0B Motor phase failure phase V Keypad display: Phase V failure
Cause Error type/response Remedy
A failure of the motor phase V has been detec-
ted.
No response (Congurable)
•
The error can only be reset aer a blocking
me.
•
Check wiring between inverter and motor.
•
In case of a false tripping, adapt the sengs
for the motor phase failure detecon.
Blocking me: 2 s
Seng parameters: 0x2D45:001 (P310.01)
Related topics
4Motor phase failure detecon ^ 236
65292 0xFF0C Motor phase failure phase W Keypad display: Phase W failure
Cause Error type/response Remedy
A failure of the motor phase W has been detec-
ted.
No response (Congurable)
•
The error can only be reset aer a blocking
me.
•
Check wiring between inverter and motor.
•
In case of a false tripping, adapt the sengs
for the motor phase failure detecon.
Blocking me: 2 s
Seng parameters: 0x2D45:001 (P310.01)
Related topics
4Motor phase failure detecon ^ 236
Diagnoscs and fault eliminaon
Error codes, causes and remedies