Installation and Commissioning
GARD 8000 SYS RFL Electronics
November 28, 2017 4-44 973.334.3100
4.6.2.11 END TO END TRIP TESTING
1. Connect the Comms Line with the Remote End.
2. Go to the ‘Settings Menu’, click on ‘Chassis Configuration’ and if necessary change the
parameters for End to End communication.
3. Using the Primitive Logic drawing apply voltage to the keying inputs at the Local End. On
the remote end observe that the appropriate trip outputs energize. The Trip TX and RX front
panel LEDs should illuminate for all tripped channels. Exercise all aspects of the primitive
and alarm logic observing all outputs for their correct response.
4. If desired, exercise all the steps described for a Local-End testing.
This ends the commissioning procedure