16.4 DNP V3.00 DEVICE PROFILE DOCUMENT
DNP V3.00
DEVICE PROFILE DOCUMENT
Vendor Name: Rfl electronics .
Highest DNP Level Supported:
For Requests Level 2
For Responses Level 2
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported
(the complete list is described in the attached table):
Maximum Data Link Frame Size (octets):
Transmitted 292
Received 292
Maximum Application Fragment Size (octets):
Transmitted 2048
Received 2048
Maximum Data Link Re-tries:
None
Maximum Application Layer Re-tries:
None
Requires Data Link Layer Confirmation:
Never
Requires Application Layer Confirmation:
Never
Timeouts while waiting for:
Data Link Confirm None
Complete Appl. Fragment None
Application Confirm Fixed at 5000 ms
Complete Appl. Response None
Sends/Executes Control Operations: