Power Line Carrier
GARD 8000 SYS RFL Electronics
April 23, 2015 10-10 973.334.3100
The operating band of the GARD is from 30kHz to 500kHz. Jumpers J3 through J11 on the Analog
Module can be set to accomplish the desired frequency range. Note that the circuit board has been
revised with the addition of jumpers J38, J39 and J40. Table 10.4 gives the assembly numbers for the
new Analog Module Assembly with various operating options followed by the jumper settings to
achieve the required frequency range. Table 10.6 gives the assembly numbers for the part number
series 500930 followed by the jumper settings to achieve the required frequency range.
Note that on the part number series 500930 the 393.5kHz to 500kHz version has no jumper
settings.
J5
J6
J3
J4
J11
J7
J8J9
J10
J39*
J38*
J40*
* Jumpers added on revised circuit board
Figure 10-4. GARD PLC Analog Module Carrier Frequency Range Jumper Settings
Table 10-4. PLC Analog Module Assembly Part Numbers (part number series 500935)