EasyManua.ls Logo

RFL Electronics GARD 8000 - SECTION 3. TECHNICAL DATA; 3.1 SYSTEM SPECIFICATIONS

RFL Electronics GARD 8000
647 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Data
GARD 8000 SYS RFL Electronics
September 24, 2012 3-1 973.334.3100
SECTION 3. TECHNICAL DATA
3.1 SYSTEM SPECIFICATIONS
As of the date this Instruction Manual was published, the following specifications apply to the GARD
8000 module. Because all of RFL products undergo constant refinement and improvement, these
specifications are subject to change without notice.
Single or Redundant Power Supply:
Wide Range: 48/125 Vdc Or 120 Vac
Range 38 - 150 Vdc Or 96 - 132 Vac
250Vdc: 220/250 Vdc Or 220 Vac
Range 200 - 300 Vdc Or 200 - 240 Vac
24Vdc: Range 19 29Vdc
Burden: Maximum 100 W With Fully Populated 6U Chassis
Terminal Connections:
Rear Screw Terminals
Inputs and Outputs:
The GARD 8000 System can be configured with up to 20 input and output modules on the rear part of the
chassis. Relay outputs are jumper selectable Form A or Form B, and in addition each input and output
has an inverter and a timer associated with it that has settings for both pick-up (debounce) delay and
drop-out (pulse-stretch) delay.
Optically Isolated Inputs:
Quantity: Six per module
Jumper selectable Input Voltage: 24/48/125/250 Vdc
Rating No operation Operates Max Input Voltage
24v <14v >19v 36v
48v <28v >38v 68v
125v <70v >95v 150v
250v <140v >189v 300v
Input current: minimum 1.5 mA
Minimum Pulse Width: 0.03 ms, additional debounce time set with logic timer settings.
Solid-State Outputs:
Quantity: Six per module
Output Current: Maximum 1 A continuous, 2 A for one minute, or 10 A for 100 msec.
Open-Circuit Voltage: 300 Vdc maximum
Pick-up Time: <1 msec
Relay Outputs:
Quantity: Six per module
Relay Pick-up Time: 4 msec
Output Current Rating: 6 A continuous
Surge: 30 A for 200 msec

Table of Contents