GARD DNP Configuration and SNMP Trap Agent
GARD 8000 SYS RFL Electronics
April 23, 2015 16-8 973.334.3100
Scale
A user entered scale. The value measured by the card will be multiplied by the number entered here.
Offset
A user entered offset added to the signal. The value measured by the card is offset by this amount after
the scale is applied.
For example:
If a measurement of 0 – 10 is to be represented as a DNP value of -20 to +20, a scale of 4 and an offset
of -20 is used.
(0 · 4) + (-20) = -20
(10 · 4) + (-20) = 20
Configuring Math Points:
Figure 16-9. Configuring Math Points