Chassis Configuration Settings
GARD 8000 SYS RFL Electronics
April 1, 2012 7-64 973.334.3100
Advanced /Logic Settings
Discriminator Energy Threshold (15) (0-100 inc 1)
This setting indicates the differential in signal level between guard and trip frequencies required to
declare a change of state. Set to 15dB for proper operation. The range is from 0dB to 100dB in 1dB
increments.
Rx Agc Setpoint (30) (10-40 inc 1)
Determines the headroom allowed in the analog section of the receiver when commissioned. Should
be set to 30.
CAUTION: Changing the following bit range settings will affect system logic.
TX Logic Bus Start Bit (3-511 inc 1)
The range of TX logic bus start bits can be set from 3 to 511 in increments of 1.
Refer to System Logic PDF for help.
TX Logic Bus Length (0-24 inc 1)
The TX logic bus length can be set from 0 to 24 in increments of 1.
Refer to System Logic PDF for help.
RX Logic Bus Start Bit (3-511 inc 1)
The range of RX logic bus start bits can be set from 3 to 511 in increments of 1.
Refer to System Logic PDF for help.
RX Logic Bus Length (0-24 inc 1)
The RX logic bus length can be set from 0 to 24 in increments of 1.
Refer to System Logic PDF for help.
Check the SAVE button to save your settings.