EasyManua.ls Logo

RFL Electronics GARD 8000 - Page 331

RFL Electronics GARD 8000
647 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chassis Configuration Settings
GARD 8000 SYS RFL Electronics
April 1, 2012 7-95 973.334.3100
Major Alarm Pickup Delay:
Once an abnormal condition is detected, as programmed in the Alarm Configurations below, the
pickup timer can be set to delay the Major Alarm indication from 0 to 30 seconds in 125ms
increments. A SOE record is generated as soon as the event occurs, regardless of the delay setting.
Major Alarm Dropout Delay:
Once an abnormal condition ceases, the dropout timer can be set to delay the ending of the Major
Alarm indication from 0 to 30 seconds in 125ms increments. A SOE record is generated as soon as the
event ends, regardless of the delay setting.
Minor Alarm Pickup Delay:
Once an abnormal condition is detected, as programmed in the Alarm Configurations below, the
pickup timer can be set to delay the Minor Alarm indication from 0 to 30 seconds in 125ms
increments. A SOE record is generated as soon as the event occurs, regardless of the delay setting.
Minor Alarm Dropout Delay:
Once an abnormal condition ceases, the dropout timer can be set to delay the ending of the Minor
Alarm indication from 0 to 30 seconds in 125ms increments. A SOE record is generated as soon as the
event ends, regardless of the delay setting.
Note: The Alarm Relays normal operating mode is energized; an alarm will be issued in an un-
energized state.
Logic Bus Error:
Will go active if a problem is detected on the logic bus. Always review the logic configuration to
ensure that no bits are being driven by more than one source.
Comm Bus 1/2:
Comm Bus 1 or Comm Bus 2 alarm will be activated if the signal is invalid. The Comms busses
should be configured before setting the alarm source. An un-configured comm bus will cause the
alarm to go active.
Logic Test Mode Active:
This alarm will become active if the user enters a logic test mode (forcing an input active for example).
Over/Under Voltage Alarm:
Alarm goes active when a power supply output voltage is measured to be outside of the acceptable
range.
HMI Output Alarm:
Assigned Output0 or Output1 on internal schematic can be mapped to an alarm that will trigger alarms
visible on the web page. (0 = No Alarm, 1 = Alarm)
Clock Quality:
Alarm will become active if the expected clock source is not synchronized. Note, source set on the
Time Settings web page.

Table of Contents