Chassis Configuration Settings
GARD 8000 SYS RFL Electronics
April 1, 2012 7-97 973.334.3100
Module:
Identifies the type of module i.e. Input, Output, TPS etc.
Module Alarm:
Identifies the type of module alarm being mapped. This is a read only field identifying the Major and
Minor module alarm.
System Alarm:
The system alarm is a drop down web page that will map the associated module alarm to the GARD
8000 system alarms. The selections are:
Major: Activates the GARD 8000 Major Alarm contact on the PS I/O when the module alarm
goes active
Minor Activates the GARD 8000 Minor Alarm contact on the PS I/O when the module alarm
goes active
Both: Activates the GARD 8000 Major and Minor Alarm contacts on the PS I/O when the
module alarm goes active
None: Does not activate either the GARD 8000 Major or Minor Alarm contacts on the PS I/O
when the module alarm goes active
Status:
Will show whether a module is in an alarm state.
Red: Alarm condition
Green: No alarm condition
Note this is independent of the System Alarm and will only show that a module is in or out of alarm, it
will not differentiate between major or minor alarms.