Tests and Diagnostics
GARD 8000 SYS RFL Electronics
February 14, 2011 11-24 973.334.3100
Configuration and alarm status information:( Read only)
User Label:
This is a user-defined label. This label can identify a line number, remote substation or any
other information that may assist in identifying the interface.
Chassis Location:
Indicates the physical location of the communications interface in the chassis. The chassis
position, slot number, and location on the interface board, top or bottom is provided.
Timing Status:
Indicates the timing source setting for the communications interface. This can be,
Slave
Module gets it’s timing source from the Communications bus.
Master Internal
Module generates the timing source for the entire communications bus. One
module on the communications bus must be programmed as the Master clock
source. The master internal setting uses the modules internal clock to generate
the clock source.
Master Recovered
Module generates the timing source for the entire communications bus. One
module on the communications bus must be programmed as the Master clock
source. The master recovered setting uses a clock source recovered from an
incoming data source, a multiplexer as an example, to generate the
communications bus clock.
Configured:
Indicates that the module is properly configured. Green indicates that the modules configured,
red indicates that the module is not configured.