Tests and Diagnostics
GARD 8000 SYS RFL Electronics
February 14, 2011 11-27 973.334.3100
Exit Loop-back:
To exit a loop-back test,
Click on the active loop-back test button.
The button will change from red and Active” to green and Disabled” and hit
Execute.
The module will remain in loop-back until the execute button is pressed.
The Loop-back” status will change from red and Active to green and Disabled.
Any system settings that were changed during testing must be returned to normal
operating before returning the equipment to service.
The minor alarm, TX Activity and RX Activity indicators will be green.
Reset error counters.
Additional status information:
GARD Communications Bus:
Identifies what communications bus, 1 or 2, the Transmit (TX) and Receive (RX) data of the
C37.94 interface module is assigned to.
GARD Communications Direction:
Identifies what communications bus direction, A or B, the Transmit (TX) and Receive (RX)
data of the C37.94 interface module is assigned to.
Interface Data Polarity:
Indicates the programmed Data polarity for the interface. Transmit and receive data can be set
for either Normal or Inverted".
Accumulated Errors:
Provides a count of total errored words since last reset.
Errors per Second:
Provides a count of the number of errored words that occurred over the last second.
Errored Seconds:
Provides a count of the total number of errored seconds since the last reset.
Reset Error Counters button:
Provides the user a means to reset the error counters of the multiprotocol module.
Time Slot Configuration Button:
The time slot configuration button allows the user to view the communications time slot
assignment of the multiprotocol module.