Applications
GARD 8000 SYS RFL Electronics
May 1, 2013 2-29 973.334.3100
2.13.1 8 KB/S REMOTE SERVICE CHANNEL
1. The 8 kb/s link is currently used over the TPS channel. Remote and local TPS channels must
be set to both Disabled or set to a Comm channel. It is not valid for one channel to be set to
Disabled and one to be set for a Comm channel.
2. The TPS channel must first be assigned in the Communication Time Slot Configuration web
page (see Figure 7-19), before remote service can be changed from Disabled to either Comm0
or Comm1 on the TPS Channel web page.
3. It is not valid to use an 8 kb/s Remote Service Channel (TPS) if the Comm’s Bus on the Master
Communication Module is set to T1/E1. A 64 kb/s Remote Service Channel must be used
instead.
2.13.2 64 KB/S REMOTE SERVICE CHANNEL
1. Interface Data must be Byte-Aligned. The following Communication Modules may use the
Remote Service Channels:
a. T1/E1.
b. G.703 Co-directional. OCTET timing mode only.
c. RS-449/X.21/V.35.
Data rate > 64 kb/s.
d. C37.94 (Short Haul Fiber).
Data rate > 64 kb/s.
e. Long-haul Fiber.
Data rate > 64 kb/s.
2. Select 64k Com0” and/or 64k Com1” on the Communication Time Slot Configuration” web
page for the desired Communication Module.
When selecting a Remote Service Channel IP address, insure that it is on the same IP sub-network as
the IP address for the GARD’s rear Ethernet port. The Remote Service Channels IP address must not
conflict with any IP address on the IP network.
NOTE
NOTE
IP address192.168.1.2 is reserved for PDA use.