Ethernet TPS Module
GARD 8000 SYS RFL Electronics
April 14, 2015 14-12 973.334.3100
A GOOSE message can bring any number of values. In this example web page the first value is
mapped to Bit 12 plus the offset set on the “General Settings” web page under TX Logic Bus Start Bit
If set to “0” that GOOSE value will not be used.
The following two settings can be used to set the binary and non-binary (analog, counters etc.) values
for each Bit.
Zero Range
In a binary application the zero range can be set to zero or one. The non binary value can be set for a
range between 0 and 99.
One Range
In a binary application the one range can be set to one or zero. The non binary value can be set for a
range between 100 and 199.
Get CID File:
When checked, a standard download prompt is displayed, click save and browse to the required saved
path location. Some browsers will require you to right click on the link and select “save target as” or a
similar prompt.
14.3.1 ETHERNET TPS MODULE GENERAL STATUS
From the Home page click the Ethernet TPS module, the following status page will appear.