EasyManua.ls Logo

Siemens SINAMICS G120X - General Converter Technical Data

Siemens SINAMICS G120X
1148 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11.3 General converter technical data
Property Explanation
Line voltage FSA … FSG:
for systems according to IEC:
3 AC 380 V (-20 %) ... 480 V (+10 %)
3 AC 500 V (-20 %) ... 690 V (+10 %)
for systems according to UL:
3 AC 380 V ... 480 V
3 AC 500 V ... 600 V
The actual permissible line voltage depends on the installation altitude.
FSH, FSJ:
3 AC 380 V (-15 %) ... 480 V (+10 %)
3 AC 500 V (-15 %) ... 690 V (+10 %)
Output voltage 0 V 3 AC ... line voltage x 0.97
Input frequency 47 Hz ... 63 Hz
Output frequency
FSA ... FSG: 0 Hz ... 550 Hz, depending on the control mode
FSH/FSJ: 0 Hz ... 150 Hz, depending on the control mode
Power factor λ
FSA ... FSG: 0.75 ... 0.93
FSH/FSJ with line reactor uk = 2 %: 0.75 ... 0.93
Line impedance uk 4 %
Inrush current < 2 × peak input current
The converter can withstand 100,000 power cycles with an inverval of 120 s.
Overvoltage category According to IEC 61800-5-1:
III for Power Module
III for Control Unit (Not for corner grounded network 380-480V AC or power supply
network >= 600V AC without electrical isolation)
1)
Line harmonics The converter fulfils the requirements of IEC 61000-3-12 with Rsce = 120.
Further technical data on request.
Pulse frequency (factory setting) FSA … FSG
400 V converters:
4 kHz for devices with an LO base load power < 100 kW
2 kHz for devices with an LO base load power ≥ 100 kW
690 V converters: 2 kHz
FSH/FSJ: 4 kHz