6.10.3 Bypass
Overview
The "Bypass" function switches the motor between converter and line operation.
..
..
.
'212

'2&20
'212
'2&20
',
',
9287
*1'
.
.
.
U
%,S>@
U
%,S>@
S
U
S
U
Figure 6-97 Bypass control via converter
Requirements
The "Bypass" function is supported only for induction motors.
The K1 converter contactor and K2 line contactor are designed for switching under load.
The K2 line contactor is designed for switching under inductive load.
The K1 converter contactor and K2 line contactor are interlocked against closing at the
same time.
The "flying restart" function must be activated (p1200 = 1 or 4).
Flying restart – switching on while the motor is running (Page 423)
$
%
&