Note
For bit 00:
The threshold value is set in p1080 and the hysteresis in p2150.
For bit 01, 02:
The threshold value is set in p2155 and the hysteresis in p2140.
For bit 03:
1 signal direction of rotation positive.
0 signal: direction of rotation negative.
The hysteresis is set in p2150.
For bit 04:
The threshold value is set in r1119 and the hysteresis in p2150.
For bit 05:
The threshold value is set in p1226 and the delay time in p1228.
For bit 06:
The hysteresis is set in p2162.
For bit 07:
The threshold value is set in p2163 and the hysteresis is set in p2164.
For bit 08:
The threshold value is set in p2170 and the delay time in p2171.
For bit 09, 10:
The threshold value is set in p2172 and the delay time in p2173.
For bit 11:
The threshold value is set in p2179 and the delay time in p2180.
For bit 13:
Only for internal Siemens use.
r2198.4...12 CO/BO: Status word monitoring 2 / ZSW monitor 2
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2536
Min:
-
Max:
-
Factory setting:
-
Description: Display and BICO output for the second status word of the monitoring functions.
Bit field: Bit Signal name 1 signal 0 signal FP
04 |n_set| < p2161 Yes No 8011
05 n_set > 0 Yes No 8011
06 Motor blocked Yes No 8012
07 Motor stalled Yes No 8012
08 |I_act| < I_threshold value p2170 Yes No 8022
11 Load in the alarm range Yes No 8013
12 Load in the fault range Yes No 8013
Note
For bit 12:
This bit is reset after the fault cause disappears, even if the fault itself is still present.
r2199.0...5 CO/BO: Status word monitoring 3 / ZSW monitor 3
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2537
Min:
-
Max:
-
Factory setting:
-
Description: Display and BICO output for the third status word of the monitoring functions.
Parameters
7.2 Parameter list
SINAMICS G120X converter
790 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC