p2286[0...n] BI: Hold technology controller integrator / Tec_ctr integ hold
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 7958
Min:
-
Max:
-
Factory setting:
56.13
Description: Sets the signal source to hold the integrator for the technology controller.
p2289[0...n] CI: Technology controller precontrol signal / Tec_ctr prectr_sig
Access level: 3 Calculated: - Data type: Unsigned32 /
FloatingPoint32
Can be changed: T, U Scaling: PERCENT Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 7958
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source for the precontrol signal of the technology controller.
p2290[0...n] BI: Technology controller limiting enable / Tec_ctrl lim enab
Access level: 2 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 7958
Min:
-
Max:
-
Factory setting:
1
Description: Sets the signal source to enable the technology controller output.
The technology controller output is enabled with a 1 signal.
The technology controller output is held with a 0 signal.
p2291 CO: Technology controller maximum limiting / Tec_ctrl max_lim
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: PERCENT Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7958
Min:
-200.00 [%]
Max:
200.00 [%]
Factory setting:
100.00 [%]
Description: Sets the maximum limit of the technology controller.
Dependency: See also: p2292
CAUTION
The maximum limit must always be greater than the minimum limit (p2291 > p2292).
p2292 CO: Technology controller minimum limiting / Tec_ctrl min_lim
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: PERCENT Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7958
Min:
-200.00 [%]
Max:
200.00 [%]
Factory setting:
0.00 [%]
Description: Sets the minimum limit of the technology controller.
Dependency: See also: p2291
CAUTION
The maximum limit must always be greater than the minimum limit (p2291 > p2292).
Parameters
7.2 Parameter list
SINAMICS G120X converter
806 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC