6.8.2 Converter protection using temperature monitoring
Overview
The converter temperature is essentially defined by the following effects:
The ambient temperature
The ohmic losses increasing with the output current
Switching losses increasing with the pulse frequency
Monitoring types
The converter monitors its temperature using the following monitoring types:
I
2
t monitoring (alarm A07805, fault F30005)
Measuring the chip temperature of the Power Module (alarm A05006, fault F30024)
Measuring the heat sink temperature of the Power Module (alarm A05000, fault F30004)
Function description
Overload response for p0290 = 0
The converter responds depending on the control mode that has been set:
In vector control, the converter reduces the output current.
In U/f control, the converter reduces the speed.
Once the overload condition has been removed, the converter re-enables the output current or
speed.
If the measure cannot prevent a converter thermal overload, then the converter switches off the
motor with fault F30024.
Overload response for p0290 = 1
The converter immediately switches off the motor with fault F30024.
Overload response for p0290 = 2
We recommend this setting for drives with square-law torque characteristic, e.g. fans.
Advanced commissioning
6.8 Drive protection
SINAMICS G120X converter
406 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC