p1269[0...1] BI: Bypass switch feedback signal / Bypass FS
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
[0] 1261.0
[1] 1261.1
Description: Sets the signal source for the feedback signal of the bypass switch.
Index: [0] = Switch motor/drive
[1] = Switch motor/line supply
Dependency: The "Bypass" function is only available for induction motors.
Note
In the case of switches without a feedback signal, interconnect the corresponding control bit as the signal source:
BI: p1269[0] = r1261.0
BI: p1269[1] = r1261.1
Entering p1269 = 0 sets this interconnection automatically for switches without a feedback signal.
p1270[0...n] Flying restart configuration / Fly restart config
G120X_DP (PM330),
G120X_PN (PM330),
G120X_USS (PM330)
Access level: 4 Calculated: - Data type: Unsigned16
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
0000 0000 0000 0011 bin
Description: Sets the configuration for the "flying restart function" function.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Fast flying restart with voltage model for induction motor Yes No -
01 PLL expansion for fast flying restart w/ voltage model for ASM Yes No -
12 Use peak current values Yes No -
13 Number of current controller cycles (test pulse) bit 0 1 0 -
14 Number of current controller cycles (test pulse) bit 1 1 0 -
15 Number of current controller cycles (test pulse) bit 2 1 0 -
Note
ASM: Induction motor
For bit 00:
This bit is equivalent to p1780 bit 11.
For bit 01:
This bit should only be set when required for large drives.
p1271[0...n] Flying restart maximum frequency for the inhibited direction / FlyRes f_max dir
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: -
Min:
0 [Hz]
Max:
650 [Hz]
Factory setting:
0 [Hz]
Description: Sets the maximum search frequency for a flying restart in an inhibited setpoint direction (p1110, p1111).
Note
The parameter has no effect for an operating mode, which only searches in the setpoint direction (p1200 > 3).
Parameters
7.2 Parameter list
SINAMICS G120X converter