Note
When a pump is in service mode, the converter locks the corresponding relay. Then you can perform troubleshooting
of this pump without interrupting the operation of other pumps.
p29542.0...5 CO/BO: Multi-pump control service mode interlock manually / Mpc ser_interl
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
0000 0000 bin
Description: Sets the service mode manually.
When a motor fault is activated or a motor is not to run, user can set the corresponding bit to 1 to lock it.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Motor 1 locked Yes No -
01 Motor 2 locked Yes No -
02 Motor 3 locked Yes No -
03 Motor 4 locked Yes No -
04 motor 5 locked Yes No -
05 motor 6 locked Yes No -
p29543[0...5] BI: Multi-pump control motor under repair / Mpc mtr_und_ser
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
[0] 29542.0
[1] 29542.1
[2] 29542.2
[3] 29542.3
[4] 29542.4
[5] 29542.5
Description: Sets the signal source(digital input or p29542) for service mode.
The signal indicates the motor/motors which is/are under repair or locked manually.
Index: [0] = Motor 1 under repair
[1] = Motor 2 under repair
[2] = Motor 3 under repair
[3] = Motor 4 under repair
[4] = Motor 5 under repair
[5] = Motor 6 under repair
r29544[0...5] Multi-pump control index of motors under repair / Mpc mtr und repair
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Parameters
7.2 Parameter list
SINAMICS G120X converter
920 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC