Description: Sets the signal source for the main setpoint.
Examples:
r1024: Fixed speed setpoint effective
r1050: Motor. potentiometer setpoint after the ramp-function generator
Dependency: See also: p1071, r1073, r1078
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1071[0...n] CI: Main setpoint scaling / Main setp scal
Access level: 3 Calculated: - Data type: Unsigned32 /
FloatingPoint32
Can be changed: T Scaling: PERCENT Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 3001, 3030
Min:
-
Max:
-
Factory setting:
1
Description: Sets the signal source for scaling the main setpoint.
r1073 CO: Main setpoint effective / Main setpoint eff
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dynamic index: -
Unit group: 3_1 Unit selection: p0505 Function diagram: 3030
Min:
- [rpm]
Max:
- [rpm]
Factory setting:
- [rpm]
Description: Displays the effective main setpoint.
The value shown is the main setpoint after scaling.
p1075[0...n] CI: Supplementary setp / Suppl setp
Access level: 3 Calculated: - Data type: Unsigned32 /
FloatingPoint32
Can be changed: T Scaling: p2000 Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 3001, 3030
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source for the supplementary setpoint.
Dependency: See also: p1076, r1077, r1078
p1076[0...n] CI: Supplementary setpoint scaling / Suppl setp scal
Access level: 3 Calculated: - Data type: Unsigned32 /
FloatingPoint32
Can be changed: T Scaling: PERCENT Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 3001, 3030
Min:
-
Max:
-
Factory setting:
1
Description: Sets the signal source for scaling the supplementary setpoint.
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 623