Table 6-10 Response identifiers, converter → control
AK Description
0 No response
1 Transfer parameter value (word)
2 Transfer parameter value (double word)
3 Transfer descriptive element
1)
4 Transfer parameter value (field, word)
2)
5 Transfer parameter value (field, double word)
2)
6 Transfer number of field elements
7 Converter cannot process the request.
In the most significant word of the parameter channel, the converter sends an error number
to the control, refer to the following table.
8 No master controller status / no authorization to change parameters of the parameter channel
interface
1)
The required element of the parameter is specified in IND (2nd word).
2)
The required element of the indexed parameter is specified in IND (2nd word).
Table 6-11 Error numbers for response identifier 7
No. Description
00 hex Illegal parameter number (access to a parameter that does not exist)
01 hex Parameter value cannot be changed (change request for a parameter value that cannot be
changed)
02 hex Lower or upper value limit exceeded (change request with a value outside the value limits)
03 hex Incorrect subindex (access to a subindex that does not exist)
04 hex No array (access with a subindex to non-indexed parameters)
05 hex Incorrect data type (change request with a value that does not match the data type of the
parameter)
06 hex Setting not permitted, only resetting (change request with a value not equal to 0 without
permission)
07 hex Descriptive element cannot be changed (change request to a descriptive element error value
that cannot be changed)
0B hex No master control (change request but with no master control, see also p0927)
0C hex Keyword missing
11 hex Request cannot be executed due to the operating state (access is not possible for temporary
reasons that are not specified)
14 hex Inadmissible value (change request with a value that is within the limits but which is illegal for
other permanent reasons, i.e. a parameter with defined individual values)
65 hex Parameter number is currently deactivated (depending on the mode of the converter)
66 hex Channel width is insufficient (communication channel is too small for response)
68 hex Illegal parameter value (parameter can only assume certain values)
6A hex Request not included / task is not supported (the valid request identifications can be found
in table "Request identifications controller → converter")
6B hex No change access for a controller that is enabled. (The operating state of the converter
prevents a parameter change)
Advanced commissioning
6.3 Drive control
SINAMICS G120X converter
214 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC