Property Object type
Binary In‐
put BI…
Binary Out‐
put BO…
Binary Val‐
ue BV…
Analog In‐
put AI…
Analog
Output
AO…
Analog
Value
AV…
Multi-State
Input
MSI…
Octet
String val‐
ues
State_Text X
Num‐
ber_of_States
X
1)
Only for access type C: Commandable
Binary Input BI…
In‐
stance
ID
Object name Description Possible val‐
ues
Text active /
text inactive
Access
type
1)
Parameter
BI0 DI0 ACT Status DI 0 ON/OFF ON/OFF R r0722.0
BI1 DI1 ACT Status DI 1 ON/OFF ON/OFF R r0722.1
BI2 DI2 ACT Status DI 2 ON/OFF ON/OFF R r0722.2
BI3 DI3 ACT Status DI 3 ON/OFF ON/OFF R r0722.3
BI4 DI4 ACT Status DI 4 ON/OFF ON/OFF R r0722.4
BI5 DI5 ACT Status DI 5 ON/OFF ON/OFF R r0722.5
BI6 DI6 ACT Status DI 6 ON/OFF ON/OFF R r0722.6
BI7 DI7 ACT Status DI 7 ON/OFF ON/OFF R r0722.7
BI8 DI7 ACT Status AI 0 - used as DI 11 ON/OFF ON/OFF R r0722.11
BI9 DI8 ACT Status AI 1 - used as DI 12 ON/OFF ON/OFF R r0722.12
BI10 DO0 ACT Status DO 0 (relay 1) ON/OFF ON/OFF R read r747.0
BI11 DO1 ACT Status DO 1 (relay 2) ON/OFF ON/OFF R read r747.1
BI12 DO2 ACT Status DO 2 (relay 3) ON/OFF ON/OFF R read r747.2
BI13 DO3 ACT Status DO 3 (relay 2) ON/OFF ON/OFF R read r747.3
BI14 DO4 ACT Status DO 4 (relay 3) ON/OFF ON/OFF R read r747.4
1)
R: Readable
Binary Output BO…
Instance
ID
Object name Description Possible val‐
ues
Text active /
text inactive
Access
type
1)
Parameter
BO0 DO0 CMD Controls DO 0 (relay 1) ON/OFF ON/OFF C p0730
BO1 DO1 CMD Controls DO 1 (relay 2) ON/OFF ON/OFF C p0731
BO2 DO2 CMD Controls DO 2 (relay 3) ON/OFF ON/OFF C p0732
BO3 DO3 CMD Controls DO 3 (relay 4) ON/OFF ON/OFF C p0733
BO4 DO4 CMD Controls DO 4 (relay 5) ON/OFF ON/OFF C p0734
BO5 DO5 CMD Controls DO 5 (relay 6) ON/OFF ON/OFF C p0735
1)
C: Commandable
Advanced commissioning
6.3 Drive control
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 281