Note
ESM: Essential Service Mode
When the essential service mode is activated, the effective speed setpoint is displayed in r1114.
For p3881 = 0:
The last known setpoint value is only transmitted safely if it was present consistently for at least 30 s prior to activating
the essential service mode. If this condition is not met, fixed speed setpoint 15 (p1015) is used.
For p3881 = 6:
n_act = 0: pulse suppression and switching on inhibited.
n_active > 0: braking along the ramp-function generator down ramp (p1121), pulse cancellation and switching on
inhibited.
For p3881 = 7:
n_act = 0: pulse suppression and switching on inhibited.
n_act > 0: immediate pulse cancellation and switching on inhibited.
p3882 ESM setpoint source alternative / ESM setp_src alt
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7033
Min:
0
Max:
2
Factory setting:
0
Description: Sets the alternative setpoint source for essential service mode (ESM).
This setpoint is used when the setpoint source set in p3881 is lost.
Value: 0: Last known setpoint (r1078 smoothed)
1: Fixed speed setpoint 15 (p1015)
2: Maximum speed (p1082)
Dependency: See also: p3881
Note
ESM: Essential Service Mode
The alternative setpoint source is only active for p3881 = 2, 3, 4.
p3883 BI: ESM direction of rotation signal source / ESM rot dir s_s
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7033
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source for the direction of rotation during essential service mode (ESM).
p3883 = 1 signal:
Direction of rotation of the setpoint, parameterized for essential service mode, is reversed.
p3883 = 0 signal:
Direction of rotation of the setpoint parameterized for essential service mode is kept.
WARNING
The direction reversal is not taken into account if p3881 = 4 is set (technology controller) and the technology controller
is also active as the setpoint source.
Note
ESM: Essential Service Mode
Parameters
7.2 Parameter list
SINAMICS G120X converter
844 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC