p1110[0...n] BI: Inhibit negative direction / Inhib neg dir
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 2505, 3040
Min:
-
Max:
-
Factory setting:
1
Description: Sets the signal source to disable the negative direction.
Dependency: See also: p1111
p1111[0...n] BI: Inhibit positive direction / Inhib pos dir
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 2505, 3040
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source to disable the positive direction.
Dependency: See also: p1110
r1112 CO: Speed setpoint after minimum limiting / n_set aft min_lim
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dynamic index: -
Unit group: 3_1 Unit selection: p0505 Function diagram: 3050
Min:
- [rpm]
Max:
- [rpm]
Factory setting:
- [rpm]
Description: Displays the speed setpoint after the minimum limiting.
Dependency: See also: p1091, p1092, p1093, p1094, p1101
p1113[0...n] BI: Setpoint inversion / Setp inv
G120X_DP,
G120X_PN
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 2441, 2442,
2505, 3040
Min:
-
Max:
-
Factory setting:
[0] 2090.11
[1] 0
[2] 0
[3] 0
Description: Sets the signal source to invert the setpoint.
Dependency: See also: r1198
CAUTION
If the technology controller is being used as the speed main setpoint (p2251 = 0), do not invert the setpoint using p1113
when the technology controller is enabled because this can cause the speed to change suddenly and lead to positive
couplings in the control loop.
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 631