Analog Input AI…
In‐
stance
ID
Object name Description Unit Range Access
type
1)
Parameter
AI0 ANALOG IN 0 Input signal AI0 V/mA converter-depend‐
ent
R r0752[0]
AI1 ANALOG IN 1 Input signal AI1 V/mA converter-depend‐
ent
R r0752[1]
AI2 ANALOG IN 2 Input signal AI2 V/mA converter-depend‐
ent
R r0752[2]
AI3 ANALOG IN 3 Input signal AI3 V/mA converter-depend‐
ent
R r0752[3]
AI10 AI 0 SCALED Scaled AI 0 input signal % converter-depend‐
ent
R r0755[0]
AI11 AIN 1 SCALED Scaled AI 1 input signal % converter-depend‐
ent
R r0755[1]
AI12 AIN 2 SCALED Scaled AI 2 input signal % converter-depend‐
ent
R r0755[2]
AI13 AIN 3 SCALED Scaled AI 3 input signal % converter-depend‐
ent
R r0755[3]
1)
R: Readable
Analog Output AO…
In‐
stance
ID
Object name Description Unit Range Access
type
1)
Parameter
AO0 ANALOG OUTPUT 0 Output signal AO 0 % converter-depend‐
ent
C p0791[0]
AO1 ANALOG OUTPUT 1 Output signal AO 1 % converter-depend‐
ent
C p0791[1]
AO2 ANALOG OUTPUT 2 Output signal AO 2 % converter-depend‐
ent
C p0791[2]
1)
C: Commandable
Binary Value BV…
Instance
ID
Object name Description Possible values Text ac‐
tive
Text in‐
active
Ac‐
cess
type
1)
Parameter
BV0 RUN / STOP
ACT
Converter status regardless of com‐
mand source
RUN / STOP STOP RUN R r0052.2
BV1 FWD / REV Direction of rotation regardless of
command source
REV / FWD FWD REV R r0052.14
BV2 FAULT ACT Converter fault FAULT / OK FAULT OK R r0052.3
BV3 WARN ACT Converter warning WARN / OK WARN OK R r0052.7
Advanced commissioning
6.3 Drive control
SINAMICS G120X converter
282 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC