Parameters
Table 6-7 Parameters for the scaling characteristic
Parameter Description Factory setting
p0777[0…1] CU analog outputs characteristic value x1 -
p0778[0…1] CU analog outputs characteristic value y1 0 V
p0779[0…1] CU analog outputs characteristic value x2 100%
p0780[0…1] CU analog outputs characteristic value y2 20 V
6.3.3 Drive control via PROFINET or PROFIBUS
6.3.3.1 Setting the address
Function description
Procedure
1. Set the address with a commissioning tool via p0918
2. Switch off the converter power supply.
3. Wait until all LEDs on the converter are dark.
4. Switch on the converter power supply again.
Your settings become effective after switching on.
The PROFIBUS address is set.
❒
6.3.3.2 Receive data and send data
Overview
Cyclic data exchange
The converter receives cyclic data from the higher-level control - and returns cyclic data to the
control.
Figure 6-10 Cyclic data exchange
Advanced commissioning
6.3 Drive control
SINAMICS G120X converter