3.4.2.1 Mounting the converter on the mounting panel
Dimensions and clearance distances - mm (in)
:LGWK
+HLJKW
+HLJKWLQFOXGLQJVKLHOGSODWH
'HSWK
$GGLWLRQDOGHSWK
&OHDUDQFH$
&OHDUDQFH%
Fram
e
size
Height Height in‐
cluding
shield
plate
Width Depth Additional depth Clearance
2)
With oper‐
ator panel
With
G120
Smart Ac‐
cess
With I/O
Extension
Module
A B lateral front
FSA 232
(9.1)
330 (13.0) 73 (2.8) 209
(8.2)
9 (0.4) 7 (0.3) 27 (1.1)
1)
80 (3.1) 100
(3.9)
0
3)
-
FSB 275
(10.8)
383 (15.1) 100
(3.9)
209
(8.2)
9 (0.4) 7 (0.3) 27 (1.1)
1)
80 (3.1) 100
(3.9)
0
3)
-
FSC 295
(11.6)
423 (16.7) 140
(5.5)
209
(8.2)
9 (0.4) 7 (0.3) 27 (1.1)
1)
80 (3.1) 100
(3.9)
0
3)
-
FSD 472
(18.6)
625 (24.6) 200
(7.9)
239
(9.4)
9 (0.4) 7 (0.3) 27 (1.1)
1)
300
(11.8)
350
(13.8)
0
3)
-
FSE 551
(21.7)
729 (28.7) 275
(10.8)
239
(9.4)
9 (0.4) 7 (0.3) 27 (1.1)
1)
300
(11.8)
350
(13.8)
0
3)
-
FSF 709
(27.9)
969 (38.1) 305
(12)
360
(14.2)
9 (0.4) 7 (0.3) 27 (1.1)
1)
300
(11.8)
350
(13.8)
0
3)
-
FSG 999
(39.3)
1255
(49.4)
305
(12)
360
(14.2)
9 (0.4) 7 (0.3) 27 (1.1)
1)
300
(11.8)
350
(13.8)
0
3)
-
Mounting
3.4 Mounting the converter
SINAMICS G120X converter
62 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC