Parameters
Table 6-3 Frequently used binector outputs (BO) of the converter
Parameter Description Factory setting
r0052[0...15] CO/BO: Status word 1 -
.00 1 signal: Ready for switching on
.01 1 signal: Ready for operation
.02 1 signal: Operation enabled
.03 1 signal: Fault active
The converter inverts signal r0052.03 if it is inter‐
connected to a digital output.
.04 0 signal: OFF2 active
.05 0 signal: OFF3 active
.06 1 signal: Switching on inhibited active
.07 1 signal: Alarm active
.08 0 signal: Deviation, setpoint/actual speed
.09 1 signal: Control request
.10 1 signal: Maximum speed (p1082) reached
.11 0 signal: I, M, P limit reached
.13 0 signal: Alarm, motor overtemperature
.14 1 signal: Motor clockwise rotation
.15 0 signal: Alarm, converter overload
r0053[0...11] CO/BO: Status word 2 -
.00 1 signal: DC braking active
.02 1 signal: Speed > minimum speed (p1080)
.06 1 signal: Speed ≥ setpoint speed (r1119)
p0730 BI: CU signal source for terminal DO 0 52.3
p0731 BI: CU signal source for terminal DO 1 52.2
p0732 BI: CU signal source for terminal DO 2 52.0
p0733 BI: CU signal source for terminal DO 3 52.7
p0734 BI: CU signal source for terminal DO 4 0
p0735 BI: CU signal source for terminal DO 5 0
Further information is provided in the parameter list.
Parameter list (Page 470)
Advanced commissioning
6.3 Drive control
SINAMICS G120X converter
194 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC