Note
For 100%, the actual value is not changed.
p2270 Technology controller actual value function / Tec_ctr ActVal fct
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7958
Min:
0
Max:
3
Factory setting:
0
Description: Setting to use an arithmetic function for the actual value signal of the technology controller.
Value: 0: Output (y) = input (x)
1: Root function (root from x)
2: Square function (x * x)
3: Cube function (x * x * x)
Dependency: See also: p2264, p2265, p2267, p2268, p2269, p2271
p2271 Technology controller actual value inversion (sensor type) / Tech_ctrl act inv
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7958
Min:
0
Max:
1
Factory setting:
0
Description: Setting to invert the actual value signal of the technology controller.
The inversion depends on the sensor type for the actual value signal.
Value: 0: No inversion
1: Inversion actual value signal
CAUTION
If the actual value inversion is incorrectly selected, then the closed-loop control with the technology controller can
become unstable and can oscillate!
Note
The correct setting can be determined as follows:
- inhibit the technology controller (p2200 = 0).
- increase the motor speed and in so doing, measure the actual value signal of the technology controller.
--> If the actual value increases as the motor speed increases, then p2271 should be set to 0 (no inversion).
--> If the actual value decreases as the motor speed increases, then p2271 should be set to 1 (the actual value signal
is inverted).
r2272 CO: Technology controller actual value scaled / Tech_ctrl act scal
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dynamic index: -
Unit group: 9_1 Unit selection: p0595 Function diagram: 7958
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description: Display and connector output for the scaled actual value signal of the technology controller.
Dependency: See also: p2264, p2265, r2266, p2267, p2268, p2269, p2270, p2271
Parameters
7.2 Parameter list
SINAMICS G120X converter
804 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC