In order to prevent inadvertent inhibition of the "STO" function in the FSA ... FSC converter, we
recommend protecting the associated switch with a cable tie.
Figure 4-26 Protection against inadvertent inhibition of the "STO" function, FSA … FSC
4.2.9 Application examples for "Safe Torque Off"
Overview
A higher-level control system is required to select the STO safety function.
Preconditions
Basic prerequisites
The digital outputs for the feedback of STO are correctly parameterized.
Setting the feedback signal for Safe Torque Off (Page 298)
The higher-level control system monitors the selection of the STO safety function and the
feedback from the converter.
Forced checking procedure (test stop):
The higher-level control system regularly selects the STO safety function and evaluates the
converter feedback signal.
We recommend that you implement a time monitoring function in the higher-level control
system, which issues an alarm if a test stop is overdue.
Wiring
4.2 Control interfaces
SINAMICS G120X converter
132 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC