p1909[0...n] Motor data identification control word / MotID STW
Access level: 3 Calculated: CALC_MOD_ALL Data type: Unsigned32
Can be changed: T Scaling: - Dynamic index: MDS, p0130
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
0000 0000 0000 0000 0000
0000 0000 0000 bin
Description: Sets the configuration for the motor data identification.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Stator inductance estimate no measurement Yes No -
02 Rotor time constant estimate no measurement Yes No -
03 Leakage inductance estimate no measurement Yes No -
05 Determine Tr and Lsig evaluation in the time range Yes No -
06 Activate vibration damping Yes No -
07 Deactivate vibration detection Yes No -
11 Deactivate pulse measurement Lq Ld Yes No -
12 Deactivate rotor resistance Rr measurement Yes No -
14 Deactivate valve interlocking time measurement Yes No -
15 Determine only stator resistance, valve voltage fault, dead
time
Yes No -
16 Short motor identification (lower quality) Yes No -
17 Measurement without control parameter calculation Yes No -
18 After motID direct transition into operation Yes No -
19 After MotID automatically save results Yes No -
20 Estimate cable resistance Yes No -
21 Calibrating the output voltage measurement Yes No -
22 Only identify circle Yes No -
23 Deactivate circle identification Yes No -
24 Circle identification with 0 and 90 degrees Yes No -
26 Measure with long cable Yes No -
Note
The following applies to permanent-magnet synchronous motors:
Without de-selection in bit 11, in the closed-loop control mode, the direct inductance LD and the quadrature inductance
Lq are measured at a low current.
When de-selecting with bit 11 or in the U/f mode, the stator inductance is measured at half the rated motor current.
If the stator is inductance is not measured but is to be estimated, then bit 0 should be set and bit 11 should be de-
selected.
Bit 19 = 1:
All parameters are automatically saved after a successful motor data identification.
If a speed controller optimization run is then selected, the parameters are only saved after this measurement has been
completed.
Bit 22 ... 24: only for reluctance motors
Bit 22 = 1:
Only that measurement is carried out that is required for the flying restart of a reluctance motor. The bit is reset after
a successful measurement
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 721