p8542[0...15] BI: Active STW1 in the BOP/IOP manual mode / STW1 act OP
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
[0] 8540.0
[1] 8540.1
[2] 8540.2
[3] 8540.3
[4] 8540.4
[5] 8540.5
[6] 8540.6
[7] 8540.7
[8] 8540.8
[9] 8540.9
[10] 8540.10
[11] 8540.11
[12] 8540.12
[13] 8540.13
[14] 8540.14
[15] 8540.15
Description: For the manual mode: Setting of the signal sources for STW1 (control word 1).
Index: [0] = ON/OFF1
[1] = OC / OFF2
[2] = OC / OFF3
[3] = Enable operation
[4] = Enable ramp-function generator
[5] = Continue ramp-function generator
[6] = Enable speed setpoint
[7] = Acknowledge fault
[8] = Jog bit 0
[9] = Jog bit 1
[10] = Master control by PLC
[11] = Direction reversal (setpoint)
[12] = Enable speed controller
[13] = Motorized potentiometer raise
[14] = Motorized potentiometer lower
[15] = CDS bit 0
p8543 CI: Active speed setpoint in the BOP/IOP manual mode / N_act act OP
Access level: 3 Calculated: - Data type: Unsigned32 /
FloatingPoint32
Can be changed: T Scaling: p2000 Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
8541[0]
Description: For the manual mode: Sets the signal source for the speed setpoint.
Parameters
7.2 Parameter list
SINAMICS G120X converter
876 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC