Note
While p0124 = 1, the READY LED flashes green/orange or red/orange with 2 Hz at the appropriate Control Unit.
p0133[0...n] Motor configuration / Motor config
Access level: 2 Calculated: - Data type: Unsigned16
Can be changed: C2(1, 3) Scaling: - Dynamic index: MDS, p0130
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
0000 bin
Description: Configuration of the motor when commissioning the motor.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Motor connection type Delta Star -
01 Motor 87 Hz operation Yes No -
Dependency: For standard induction motors (p0301 > 10000), bit 0 is automatically pre-assigned the connection type of the selected
data set.
For p0100 > 0 (60 Hz rated motor frequency), it is not possible to select bit 1.
See also: p0304, p0305, p1082
Note
For bit 00:
When changing the bits, the rated motor voltage p0304 and the rated motor current p0305 are automatically converted
to the selected connection type (star/delta).
For bit 01:
87 Hz operation is only possible in the delta connection type. When selected, the maximum speed p1082 is
automatically pre-assigned for a maximum output frequency of 87 Hz.
p0170 Number of Command Data Sets (CDS) / CDS count
Access level: 2 Calculated: - Data type: Unsigned8
Can be changed: C2(15) Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 8560
Min:
2
Max:
4
Factory setting:
2
Description: Sets the number of Command Data Sets (CDS).
Dependency: See also: p0010, r3996
NOTICE
When the data sets are created, short-term communication interruptions may occur.
Note
It is possible to toggle between command parameters (BICO parameters) using this data set changeover.
p0180 Number of Drive Data Sets (DDS) / DDS count
Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: C2(15) Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 8565
Min:
1
Max:
4
Factory setting:
1
Description: Sets the number of Drive Data Sets (DDS).
Dependency: See also: p0010, r3996
NOTICE
When the data sets are created, short-term communication interruptions may occur.
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 499