r0050.0...1 CO/BO: Command Data Set CDS effective / CDS effective
Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 8560
Min:
-
Max:
-
Factory setting:
-
Description: Displays the effective Command Data Set (CDS).
Bit field: Bit Signal name 1 signal 0 signal FP
00 CDS effective bit 0 ON OFF -
01 CDS effective bit 1 ON OFF -
Dependency: See also: p0810, p0811, r0836
Note
The Command Data Set selected using a binector input (e.g. p0810) is displayed using r0836.
r0051.0...1 CO/BO: Drive Data Set DDS effective / DDS effective
Access level: 2 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 8565
Min:
-
Max:
-
Factory setting:
-
Description: Displays the effective Drive Data Set (DDS).
Bit field: Bit Signal name 1 signal 0 signal FP
00 DDS effective bit 0 ON OFF -
01 DDS effective bit 1 ON OFF -
Dependency: See also: p0820, p0821, r0837
Note
When selecting the motor data identification routine and the rotating measurement, the drive data set changeover is
suppressed.
r0052.0...15 CO/BO: Status word 1 / ZSW 1
Access level: 2 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description: Display and connector output for status word 1.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Ready for switching on Yes No -
01 Ready Yes No -
02 Operation enabled Yes No -
03 Fault present Yes No -
04 Coast down active (OFF2) No Yes -
05 Quick Stop active (OFF3) No Yes -
06 Switching on inhibited active Yes No -
07 Alarm present Yes No -
08 Deviation setpoint/actual speed No Yes -
09 Control request Yes No -
10 Maximum speed reached Yes No -
Parameters