p2025[0...4] Fieldbus interface BACnet settings / BACnet setting
G120X_USS Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9310
Min:
0
Max:
4194303
Factory setting:
[0] 1
[1] 5
[2] 3
[3] 32
[4] 0
Description: Sets the parameter for communication via BACnet.
p2025[0]:
Device object instance number (0 ... 4194303).
p2025[1]:
Maximum number of info frames (1 ... 10).
p2025[2]:
Number of APDU retries (0 ... 39).
p2025[3]:
Maximum master address (1 ... 127).
Index: [0] = Device object instance number
[1] = Maximum number of info frames
[2] = Number of APDU retries
[3] = Maximum master address
[4] = Reserved
Dependency: See also: p2030
p2026[0...74] Fieldbus interface BACnet COV increment / BACnet COV incr
G120X_USS Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9310
Min:
0
Max:
4194303
Factory setting:
1
Description: Sets BACnet COV (change of value) increment values.
Parameters
7.2 Parameter list
SINAMICS G120X converter
738 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC