EasyManua.ls Logo

Siemens SINAMICS G120X - CI: Technology Controller Kp Adaptation Scaling Signal Source; Technology Controller Kp Adaptation Lower Starting Point; Technology Controller Kp Adaptation Upper Starting Point; Technology Controller Kp Adaptation Upper Value; Kp Adapt Upper Val

Siemens SINAMICS G120X
1148 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
p2312 Technology controller Kp adaptation upper value / Kp adapt upper val
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7959
Min:
0.000
Max:
1000.000
Factory setting:
10.000
Description: Sets the upper value for the adaptation of proportional gain Kp for the technology controller.
Dependency: See also: p2310, p2311, p2313, p2314, p2315, r2316
CAUTION
The upper value must be set higher than the lower value (p2312 > p2311).
Note
Kp adaptation is activated with p2252.7 = 1.
p2313 Technology controller Kp adaptation lower starting point / Kp adapt lower pt
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: PERCENT Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7959
Min:
0.00 [%]
Max:
400.00 [%]
Factory setting:
0.00 [%]
Description: Sets the lower starting point for the adaptation of proportional gain Kp for the technology controller.
Dependency: See also: p2310, p2311, p2312, p2314, p2315, r2316
CAUTION
The upper starting point must be set higher than the lower starting point (p2314 > p2313).
Note
Kp adaptation is activated with p2252.7 = 1.
p2314 Technology controller Kp adaptation upper starting point / Kp adapt upper pt
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: PERCENT Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7959
Min:
0.00 [%]
Max:
400.00 [%]
Factory setting:
100.00 [%]
Description: Sets the upper activation point for the adaptation of proportional gain Kp for the technology controller.
Dependency: See also: p2310, p2311, p2312, p2313, p2315, r2316
CAUTION
The upper starting point must be set higher than the lower starting point (p2314 > p2313).
Note
Kp adaptation is activated with p2252.7 = 1.
p2315 CI: Technology controller Kp adaptation scaling signal source / Kp adapt scal s_s
Access level: 3 Calculated: - Data type: Unsigned32 /
FloatingPoint32
Can be changed: T Scaling: PERCENT Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7959
Min:
-
Max:
-
Factory setting:
1
Description: Sets the signal source to scale the results of the adaptation of the proportional gain Kp for the technology controller.
Parameters
7.2 Parameter list
SINAMICS G120X converter
810 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC

Table of Contents

Other manuals for Siemens SINAMICS G120X

Related product manuals