EasyManua.ls Logo

Siemens SINAMICS G120X - BI: 1 St Acknowledge Faults; 1 St Acknowledge

Siemens SINAMICS G120X
1148 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Note
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
The fault response can only be changed for faults with the appropriate identification.
Example:
F12345 and fault response = NONE (OFF1, OFF2)
--> The fault response NONE can be changed to OFF1 or OFF2.
For value = 1 (OFF1):
Braking along the ramp-function generator down ramp followed by a pulse inhibit.
For value = 2 (OFF2):
Internal/external pulse inhibit.
For value = 3 (OFF3):
Braking along the OFF3 down ramp followed by a pulse inhibit.
For value = 5 (STOP2):
n_set = 0
For value = 6 (armature short-circuit, internal/DC braking):
This value can only be set for all drive data sets when p1231 = 4.
a) DC braking is not possible for synchronous motors.
b) DC braking is possible for induction motors.
p2103[0...n] BI: 1st acknowledge faults / 1st acknowledge
G120X_DP,
G120X_PN
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T, U Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 2441, 2442,
2443, 2447, 2475, 2546, 9220,
9677, 9678
Min:
-
Max:
-
Factory setting:
[0] 2090.7
[1] 0
[2] 2090.7
[3] 2090.7
Description: Sets the first signal source to acknowledge faults.
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note
A fault acknowledgment is triggered with a 0/1 signal.
p2103[0...n] BI: 1st acknowledge faults / 1st acknowledge
G120X_USS Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T, U Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 2441, 2442,
2443, 2447, 2475, 2546, 9220,
9677, 9678
Min:
-
Max:
-
Factory setting:
0
Description: Sets the first signal source to acknowledge faults.
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note
A fault acknowledgment is triggered with a 0/1 signal.
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 765

Table of Contents

Other manuals for Siemens SINAMICS G120X

Related product manuals