Value: 0: Monitoring switched out
1: Monitoring torque and load drop
2: Monitoring speed and load drop
3: Monitoring load drop
4: Monitoring pump and load failure
5: Monitoring fan and load failure
Dependency: See also: p2182, p2183, p2184, p2185, p2186, p2187, p2188, p2189, p2190, p2192, r2198, p3230, p3231, p3232
See also: A07891, A07892, A07893, F07894, F07895, F07896, F07898, A07920, A07921, A07922, F07923, F07924,
F07925, F07936
Note
p2193 = 4, 5 can only be combined with p2181 = 7, 8.
r2197.0...13 CO/BO: Status word monitoring 1 / ZSW monitor 1
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2534
Min:
-
Max:
-
Factory setting:
-
Description: Display and BICO output for the first status word of the monitoring functions.
Bit field: Bit Signal name 1 signal 0 signal FP
00 |n_act| <= n_min p1080 Yes No 8022
01 |n_act| <= speed threshold value 2 p2155 Yes No 8010
02 |n_act| > speed threshold value 2 p2155 Yes No 8010
03 n_act >= 0 Yes No 8011
04 |n_act| >= n_set Yes No 8022
05 |n_act| <= n_standstill p1226 Yes No 8022
06 |n_act| > n_max Yes No 8010
07 Speed setpoint - actual value deviation in tolerance t_off Yes No 8011
08 I_act >= I_threshold value p2170 Yes No 8022
09 Vdc_act <= Vdc_threshold value p2172 Yes No 8022
10 Vdc_act > Vdc_threshold value p2172 Yes No 8022
11 Output load is not present Yes No 8022
13 |n_act| > n_max (F07901) Yes No -
NOTICE
For bit 06:
When the overspeed is reached, this bit is set and F07901 output immediately following this. The bit is canceled again
as soon as the next pulse inhibit is present.
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 789