● IND, bit 0 … 7 (page index): = 0 hex (offset 0 corresponds to 0 hex)
● PWE1, Bit 0 … 15: = 2D2 hex (722 = 2D2 hex)
● PWE2, Bit 10 … 15: = 3F hex (drive object - for SINAMICS G120, always 63 = 3f hex)
● PWE2, Bit 0 … 9: = 2 hex (Index of Parameter (DI 2 = 2))
3DUDPHWHUFKDQQHO
3:(KLJKUGZRUG3:(ORZWKZRUG,1'QGZRUG
3DJHLQGH[3DUDPHWHUQXPEHU6XELQGH[3DUDPHWHUYDOXH
3.(VWZRUG
'ULYH2EMHFW,QGH[$.
Figure 6-14 Parameter channel to assign digital input 2 with ON/OFF1
Advanced commissioning
6.3 Drive control
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 217