Description: Displays the commissioning steps that have been carried out.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Motor/control parameters calculated (p0340 = 1, p3900 > 0) Yes No -
02 Motor data identification carried out at standstill (p1910 = 1) Yes No -
03 Rotating measurement carried out (p1960 = 1, 2) Yes No -
08 Identified motor data are automatically backed up Yes No -
11 Automatic parameterization as Standard Drive Control Yes No -
12 Automatic parameterization as Dynamic Drive Control Yes No -
14 First motor commissioning Yes No -
15 Equivalent circuit diagram parameters changed Yes No -
18 Circle identification executed Yes No -
Note
The individual bits are only set if the appropriate action has been initiated and successfully completed.
The identification final display is reset when changing the type plate parameters.
r3926[0...n] Voltage generation alternating base voltage amplitude / U_gen altern base
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dynamic index: MDS, p0130
Unit group: - Unit selection: - Function diagram: -
Min:
- [V]
Max:
- [V]
Factory setting:
- [V]
Description: Displays the base voltage for the alternating voltage in the context of motor data identification.
0:
No alternating voltages. The function is deactivated.
<0:
Automatic determination of the base voltage and wobbulation / self-setting based on the converter and the connected
motor.
Otherwise:
Base voltage for alternating current generation in volts (wobbulation active).
r3927[0...n] Motor data identification control word / MotID STW
Access level: 3 Calculated: CALC_MOD_ALL Data type: Unsigned32
Can be changed: - Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description: Successfully completed component of the last motor data identification carried out.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Stator inductance estimate no measurement Yes No -
02 Rotor time constant estimate no measurement Yes No -
03 Leakage inductance estimate no measurement Yes No -
05 Determine Tr and Lsig evaluation in the time range Yes No -
06 Activate vibration damping Yes No -
07 Deactivate vibration detection Yes No -
11 Deactivate pulse measurement Lq Ld Yes No -
12 Deactivate rotor resistance Rr measurement Yes No -
14 Deactivate valve interlocking time measurement Yes No -
15 Determine only stator resistance, valve voltage fault, dead
time
Yes No -