r1482 CO: Speed controller I torque output / n_ctrl I-M_outp
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2003 Dynamic index: -
Unit group: 7_1 Unit selection: p0505 Function diagram: 5040, 5042,
5210, 6030, 6040
Min:
- [Nm]
Max:
- [Nm]
Factory setting:
- [Nm]
Description: Display and connector output for the torque setpoint at the output of the I speed controller.
r1493 CO: Moment of inertia total, scaled / M_inert tot scal
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dynamic index: -
Unit group: 25_1 Unit selection: p0100 Function diagram: 6031
Min:
- [kgm²]
Max:
- [kgm²]
Factory setting:
- [kgm²]
Description: Display and connector output for the parameterized total moment of inertia.
The value is calculated as follows: (p0341 * p0342) + p1496
p1496[0...n] Acceleration precontrol scaling / a_prectrl scal
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: 6020, 6031
Min:
0.0 [%]
Max:
10000.0 [%]
Factory setting:
0.0 [%]
Description: Sets the scaling for the acceleration precontrol of the speed/velocity controller.
Dependency: See also: p0341, p0342
WARNING
The acceleration precontrol r1518 is kept at the old value if the ramp-function generator tracking (r1199.5) is active or
the ramp-function generator output is set (r1199.3). This is used to avoid torque peaks. Depending on the application,
it may therefore be necessary to disable the ramp-function generator tracking (p1145 = 0) or the acceleration
precontrol (p1496 = 0).
The acceleration precontrol is set to zero, if the Vdc control is active (r0056.14/15).
Note
The parameter is set to 100% by the rotating measurement (refer to p1960).
The acceleration precontrol may not be used if the speed setpoint manifests significant ripple (e.g. analog setpoint) and
the rounding-off in the speed ramp-function generator is disabled.
We also recommend that the precontrol mode is not used if there is gearbox backlash.
p1496[0...n] Acceleration precontrol scaling / a_prectrl scal
G120X_DP (PM330),
G120X_PN (PM330),
G120X_USS (PM330)
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: 6020, 6031
Min:
0.0 [%]
Max:
10000.0 [%]
Factory setting:
100.0 [%]
Description: Sets the scaling for the acceleration precontrol of the speed/velocity controller.
Dependency: See also: p0341, p0342
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 683