EasyManua.ls Logo

Siemens SINAMICS G120X - Drive Control Via Bacnet MS;TP; Bacnet Properties; Telegram, to Activate the Automatic Restart with P1210 = 26; Telegram, to Assign DI 2 with ON;OFF1

Siemens SINAMICS G120X
1148 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PWE1, bit 0 … 15: = 0 hex
PWE2, bit 0 … 15: = 1A hex (26 = 1A hex)
3DUDPHWHUFKDQQHO
3:(KLJKUGZRUG3:(ORZWKZRUG,1'QGZRUG
3DJHLQGH[3DUDPHWHUQXPEHU6XELQGH[3DUDPHWHUYDOXHELW3DUDPHWHUYDOXHELW
3.(VWZRUG
$.


Figure 6-25 Telegram, to activate the automatic restart with p1210 = 26
Write request: Assign digital input 2 with the function ON/OFF1 (p0840[1] = 722.2)
In order to link digital input 2 with ON/OFF1, you must assign parameter p0840[1] (source, ON/
OFF1) the value 722.2 (DI 2). To do this, you must fill the telegram of the parameter channel as
follows:
PKE, bit 12 … 15 (AK): = 7 hex (change parameter value (field, word))
PKE, bit 0 … 10 (PNU): = 348 hex (840 = 348 hex, no offset, as 840 < 1999)
IND, bit 8 … 15 (page index): = 0 hex (offset 0 corresponds to 0 hex)
IND, bit 0 … 7 (subindex): = 1 hex (command data set CDS1 = index1)
PWE1, bit 0 … 15: = 2D2 hex (722 = 2D2 hex)
PWE2, bit 10 … 15: = 3f hex (drive object - for SINAMICS G120 always 63 = 3f hex)
PWE2, bit 0 … 9: = 2 hex (index or bit number of the parameter: DI 2 = r0722.2)
3DUDPHWHUFKDQQHO
3:(KLJKUGZRUG3:(ORZWKZRUG,1'QGZRUG
3DJHLQGH[3DUDPHWHUQXPEHU6XELQGH[3DUDPHWHUYDOXH
3.(VWZRUG
'ULYH2EMHFW,QGH[$.


Figure 6-26 Telegram, to assign DI 2 with ON/OFF1
6.3.7 Drive control via BACnet MS/TP
6.3.7.1 BACnet properties
Function description
In BACnet, components and systems are considered to be black boxes which contain a number
of objects. BACnet objects only stipulate the behavior outside the device, BACnet sets no
internal functions.
A range of object types and their instances represent one component.
Each BACnet device has precisely one BACnet device object. An NSAP (Network Service
Access Point - comprising network number and MAC address; MAC: Medium Access Control)
uniquely identifies a BACnet device. This address is BACnet-specific and must not be confused
with the Ethernet MAC address.
Advanced commissioning
6.3 Drive control
SINAMICS G120X converter
274 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC

Table of Contents

Other manuals for Siemens SINAMICS G120X

Related product manuals