6.10.2 ECO mode
Overview
ECO mode works by slightly changing the output voltage either up or down in order to find the
minimum input power. It is suitable for applications with a low dynamic response and constant
speed setpoint, and allows energy savings of up to 40% in the ideal case.
Precondition
The ECO mode can only work under conditions when the load characteristic is low dynamic.
The ECO mode works only in U/f control mode.
In the ECO mode, active slip compensation is necessary. Set the slip compensation (p1335) to
100 %. In the event of minor fluctuations in the setpoint, you have to raise the ramp-function
generator tolerance using p1148.
Function description
ECO mode activation:
When the speed setpoint is reached and remains unchanged for 5 s, the converter
automatically reduces its output voltage to optimize the motor's operating point.
ECO mode deactivation:
ECO mode is deactivated when the setpoint changes or if the converter’s DC-link voltage is too
high or too low.
(&2OLQHDU(&2TXDGUDWLF
(&2
IDFWRU
(&2
IDFWRU
99
II
Parameters
Number Name Factory setting
p1300 Open-loop/closed-loop control operating mode 20: Speed control
(encoderless)
r1348 CO: U/f control Eco factor actual value --
For more information about the parameters, see Chapter "Parameters (Page 467)".
Advanced commissioning
6.10 Energy saving
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 437