Note
From the signal source set via the connector input, the corresponding lower 16 bits are converted.
p2099[0...1] together with r2094.0...15 and r2095.0...15 forms two connector-binector converters:
Connector input p2099[0] to binector output in r2094.0...15
Connector input p2099[1] to binector output in r2095.0...15
p2100[0...19] Change fault response fault number / Chng resp F_no
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 8050, 8075
Min:
0
Max:
65535
Factory setting:
0
Description: Selects the faults for which the fault response should be changed
Dependency: The fault is selected and the required response is set under the same index.
See also: p2101
Note
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
p2101[0...19] Change fault response response / Chng resp resp
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 8050, 8075
Min:
0
Max:
6
Factory setting:
0
Description: Sets the fault response for the selected fault.
Value: 0: NONE
1: OFF1
2: OFF2
3: OFF3
5: STOP2
6: Internal armature short-circuit / DC braking
Dependency: The fault is selected and the required response is set under the same index.
See also: p2100
NOTICE
For the following cases, it is not possible to re-parameterize the fault response to a fault:
- fault number does not exist (exception value = 0).
- Message type is not "fault" (F).
- fault response is not permissible for the set fault number.
Parameters
7.2 Parameter list
SINAMICS G120X converter