Index: [0] = Number of error-free telegrams
[1] = Number of rejected telegrams
[2] = Number of framing errors
[3] = Number of overrun errors
[4] = Number of parity errors
[5] = Number of starting character errors
[6] = Number of checksum errors
[7] = Number of length errors
p2030 Field bus interface protocol selection / Field bus protocol
G120X_DP Access level: 1 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9310
Min:
0
Max:
3
Factory setting:
3
Description: Sets the communication protocol for the field bus interface.
Value: 0: No protocol
3: PROFIBUS
Note
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
p2030 Field bus interface protocol selection / Field bus protocol
G120X_PN Access level: 1 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9310
Min:
0
Max:
10
Factory setting:
7
Description: Sets the communication protocol for the field bus interface.
Value: 0: No protocol
7: PROFINET
10: EtherNet/IP
Note
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
p2030 Field bus interface protocol selection / Field bus protocol
G120X_USS Access level: 1 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9310
Min:
0
Max:
5
Factory setting:
0
Description: Sets the communication protocol for the field bus interface.
Value: 0: No protocol
1: USS
2: Modbus RTU
5: BACnet MS/TP
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 741