p2118[0...19] Change message type message number / Chng type msg_no
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 8050, 8075
Min:
0
Max:
65535
Factory setting:
0
Description: Selects faults or alarms for which the message type should be changed.
Dependency: Selects the fault or alarm selection and sets the required type of message realized under the same index.
See also: p2119
Note
Re-parameterization is also possible if a message is present. The change only becomes effective after the message
has gone.
p2119[0...19] Change message type type / Change type type
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 8050, 8075
Min:
1
Max:
3
Factory setting:
1
Description: Sets the message type for the selected fault or alarm.
Value: 1: Fault (F)
2: Alarm (A)
3: No message (N)
Dependency: Selects the fault or alarm selection and sets the required type of message realized under the same index.
See also: p2118
Note
Re-parameterization is also possible if a message is present. The change only becomes effective after the message
has gone.
The message type can only be changed for messages with the appropriate identification (exception, value = 0).
Example:
F12345(A) --> Fault F12345 can be changed to alarm A12345.
In this case, the message number that may be possibly entered in p2100[0...19] and p2126[0...19] is automatically
removed.
r2120 CO: Sum of fault and alarm buffer changes / Sum buffer changed
Access level: 4 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 8065
Min:
-
Max:
-
Factory setting:
-
Description: Displays the sum of all of the fault and alarm buffer changes in the drive unit.
Dependency: See also: r0944, r2121
r2121 CO: Counter alarm buffer changes / Alrm buff changed
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 8065
Min:
-
Max:
-
Factory setting:
-
Parameters
7.2 Parameter list
SINAMICS G120X converter
770 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC