p0870 BI: Close main contactor / Close main cont
Access level: 2 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source to close the main contactor.
Note
The main contactor is also closed when the converter is switched on after issuing the necessary enable signals. A
binector input p0870 = 1 signal prevents the main contactor from being opened when enable signals are withdrawn.
r0898.0...10 CO/BO: Control word sequence control / STW seq_ctrl
Access level: 2 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2501
Min:
-
Max:
-
Factory setting:
-
Description: Display and connector output for the control word of the sequence control.
Bit field: Bit Signal name 1 signal 0 signal FP
00 ON/OFF1 Yes No -
01 OC / OFF2 Yes No -
02 OC / OFF3 Yes No -
03 Enable operation Yes No -
04 Enable ramp-function generator Yes No -
05 Continue ramp-function generator Yes No -
06 Enable speed setpoint Yes No -
08 Jog 1 Yes No 3001
09 Jog 2 Yes No 3001
10 Master control by PLC Yes No -
Note
OC: Operating condition
r0899.0...11 CO/BO: Status word sequence control / ZSW seq_ctrl
Access level: 2 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2503
Min:
-
Max:
-
Factory setting:
-
Description: Display and BICO output for the status word of the sequence control.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Ready for switching on Yes No -
01 Ready Yes No -
02 Operation enabled Yes No -
03 Jog active Yes No -
04 No coasting active OFF2 inactive OFF2 active -
05 No Quick Stop active OFF3 inactive OFF3 active -
06 Switching on inhibited active Yes No -
07 Drive ready Yes No -
Parameters
7.2 Parameter list
SINAMICS G120X converter
596 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC