r0039[0...2] CO: Energy display / Energy display
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
- [kWh]
Max:
- [kWh]
Factory setting:
- [kWh]
Description: Displays the energy values at the output terminals of the power unit.
Recommendation: r0042 should be used as process energy display. R0039 supplies as Bico source floating point values in Ws.
Index: [0] = Energy balance (sum)
[1] = Energy drawn
[2] = Energy fed back
Dependency: See also: p0040
Note
For index 0:
Difference between the energy drawn and energy that is fed back.
p0040 Reset energy consumption display / Energy usage reset
Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0
Max:
1
Factory setting:
0
Description: Setting to reset the display in r0039 and r0041.
Procedure:
Set p0040 = 0 --> 1
The displays are reset and the parameter is automatically set to zero.
Dependency: See also: r0039
Note
When this display is reset (p0040), then the process energy display (r0042) is also reset.
r0041 Energy consumption saved / Energy cons saved
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
- [kWh]
Max:
- [kWh]
Factory setting:
- [kWh]
Description: Displays the saved energy referred to 100 operating hours.
Dependency: See also: p0040
Note
This display is used for a fluid-flow machine.
The flow characteristic is entered into p3320 ... p3329.
For an operating time of below 100 hours, the display is interpolated up to 100 hours.
r0042[0...2] CO: Process energy display / Proc energy disp
Access level: 2 Calculated: - Data type: Integer32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
- [Wh]
Max:
- [Wh]
Factory setting:
- [Wh]
Parameters
7.2 Parameter list
SINAMICS G120X converter
480 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC