Loading...
Note
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
p8991 USB memory access / USB mem acc
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
1
Max:
2
Factory setting:
1
Description: Selects the storage medium for access via the USB mass storage.
Value: 1: Memory card
2: Flash r/w internal
Note
A change only becomes effective after a POWER ON.
The parameter is not influenced by setting the factory setting.
p8999 USB functionality / USB Fct
Access level: 4 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
1
Max:
3
Factory setting:
3
Description: Setting the USB functionality.
Value: 1: USS commissioning via the virtual COM port
2: Only memory access
3: USB commissioning and memory access
Note
COMM: Commissioning.
A change only becomes effective after a POWER ON.
The parameter is not influenced by setting the factory setting.
p9400 Safely remove memory card / Mem_card rem
Access level: 2 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0
Max:
100
Factory setting:
0
Description: Setting and display when memory card is "removed safely".
Procedure:
Setting p9400 = 2 results in a value of 3
--> The memory card can be removed safely. After removal the value sets itself to 0 automatically.
Setting p9400 = 2 results in a value of 100
--> The memory card cannot be removed safely. Removal may destroy the file system on the memory card. It may be
necessary to set p9400 = 2 again.
Value: 0: No memory card inserted
1: Memory card inserted
2: Request "safe removal" of the memory card
3: "Safe removal" possible
Parameters